Parameters | Parameter Mark | Parameter meaning | Default value | value range |
00 | U | Internal parameter | 400 | No change |
01 | CU | Special Parameter | CU6V | No change |
02 | dU | Internal parameter, automatic control | DuHH | No change |
03 | HP | Current phase position identify, to identify wired current direction Need/no need HPYY /HPNO |
HPYY | HPYY/HPnO |
0 | 0 | Power factor at synchronized state | 0.85 | 0.55-0.99 |
1 | 1H | De-excitation frequency select | 43 | 30-45 |
2 | 2 | Generator start over excitation voltage set Prevent start exciting voltage from going too high, the smaller value, the lower generator start voltage. | 1.56 | 0.9-3.6 |
3 | 3 | Internal parameter | 0.3 | No need change |
4 | 4 | Internal parameter | 5.76 | No need change |
5' | No mark | Internal parameter | 400 | No change |
6 | 6 | Current transformer prime and second current ratio | 100 | 20-900 |
6' | 6b | Generator rated current vs current transformer prime current in percentage | 80 | 30-99 |
7 | 7P | Generator Voltage tracking speed before synchronizing, smaller value, slower adjustment, more stable. | 3 | 1-16 |
8 | 8I | Adjustment coefficient (integrate) | 6 | 1-16 |
9 | 9P | Adjustment coefficient (differential) | 5 | 1-16 |
10 | AC | Synchronized and islanding parallel operation setting. When value is 0, enter island operation (disconnect Grid in island operation), when value is 1-16, enter constant power factor automatic operation, the bigger value, the faster PF adjustment | 5 | 1-16 |
11 | BE | Internal parameter, for master computer control use | 01 | No meaning for normal user |